Abstract
A recently proposed direct Displacement-based procedure of nonlinear static (pushover) analysis on multi-storey reinforced concrete (r/c) buildings is verified here against the results of nonlinear response history analysis. An asymmetric, regular in elevation, torsionally flexible, multi-storey r/c building designed according to Eurocode EN 1998 is investigated. Taking fully into account the inelastic torsion and the higher mode effects, as well as the P-Delta effects, the proposed procedure applies a pattern of seismic floor enforced-displacements along the “Capable Near Collapse Principal Axes of the building”, aiming at the Near Collapse state. The envelope of the results of sixteen final 
Keywords
1. Introduction
The main weakness of the nonlinear static (pushover) procedure proposed by the contemporary seismic codes, as is Eurocode EN 1998-1, is its inability to properly predict the seismic interstorey drift ratios over the height of multistorey r/c buildings. Indeed, the interstorey drift ratios of asymmetric multi-storey buildings are the most representative response measure that controls the distribution of the local inelastic deformations of the structural elements, in plan and in height of the multistorey building, and hence of the structural damage[1,2]. Interstorey drift ratios are usually underestimated by the code-proposed pushover procedure due to the consideration that the building response is controlled only by the fundamental mode, ignoring the contribution of the higher and torsional modes that develop in the linear area and significantly affect the behavior in the non-linear area of response. Another weakness of the code-proposed pushover procedure is the use of the superposition technique on nonlinear analyses results, into the nonlinear area of response, to consider the spatial seismic action[3]. Additionally, the lack of proposals by the seismic codes about the main loading directions of buildings as well as for the proper consideration of the torsional sensitivity of buildings in pushover analysis raises questions about the correct/rational application of the pushover procedure. The last two issues are directly affected by the lack of definition on the one hand of the real inelastic centre of stiffness and on the other hand of the real inelastic torsional radii of the multi-storey buildings, which are continuously alter in the non-linear response region. These issues have been investigated recently by Bakalis and Makarios[4-7], Makarios and Bakalis[8,9] and Bakalis et al.[10]. Lastly, P-Delta effects should always be considered in the framework of non-linear analysis, an issue which is not emphasized enough in the seismic codes.
To deal with the inelastic torsion or/and the contribution of higher modes in the linear (and maybe into the nonlinear) response of buildings, a large number of improved pushover procedures have been developed the last two decades. These procedures use either an invariable loading vector or a variable one, usually consisting of monotonically increasing floor forces and torques (Forced-based procedures) but in some cases also of floor enforced displacements (Direct Displacement-based procedures). The first category includes the multi-mode procedures[11-17], pushover procedures combined with some kind of linear dynamic analysis[18-21] and pushover procedures that use dynamic or corrective eccentricities in order to apply the floor lateral loads[4-6,8,10,22,23]. The adaptive pushover procedures[24-29] belong to the second category. The effectiveness of the improved pushover procedures on the seismic assessment of buildings is discussed in several published research papers[30-36]. The computational cost and the complexity of implementing some of the improved pushover procedures is another important issue to emphasize, as simplicity and clearness are key points in order to have a useful tool for the assessment of the seismic capacity of structures.
To provide a comprehensive treatment of all the previously mentioned weaknesses of the code-proposed pushover procedure on multi-storey reinforced concrete (r/c) buildings, a simple Direct Displacement-based pushover procedure has been recently proposed by Makarios and Bakalis[10], Bakalis and Makarios[7]. According to this procedure, three seismic enforced-displacements are applied at each floor-diaphragm with respect to an ideal inelastic principal reference system of the multi-storey r/c building: two floor enforced-translations and one floor-enforced rotation. These seismic, drift-based, floor enforced-displacements are the outcome of a large parametric analysis on multi-storey r/c buildings and aim directly at the seismic performance level of Near Collapse (NC). Using all possible sign combinations of the three floor enforced displacements, eight final pushover analyses are performed along each main loading direction and the envelope of a total of sixteen analyses provides an accurate prediction of the seismic demand, especially as regards the distribution in-plan and in-elevation of the seismic interstorey drift ratios. Key point of the process is the definition of an ideal inelastic principal reference system of the multi-storey r/c building (CRsec (Isec, IIsec, IIIsec)) at the Near Collapse state, by considering that all the structural members have developed plastic hinges at their two ends. This reference system is called as “Capable Near Collapse Principal System of the multi-storey r/c building”. Also, the torsional sensitivity of the 
It is noted that, the effectiveness of the proposed pushover procedure with enforced displacements has been fully verified in the first author’s doctoral dissertation[37]. Various regular in elevation, ductile, multistorey r/c buildings were examined there, with varying number of floors, structural type, static eccentricity, and torsional sensitivity. In this paper, the effectiveness of the proposed procedure is verified by the seismic assessment of an asymmetric, torsionally flexible, six-storey r/c building using the nonlinear response history analysis.
2. Application Steps of the Enforced-Displacement Pushover Procedure
The basic steps for the application of the enforced-displacement pushover procedure are summarized here. It is noted that the proposed procedure follows the rationale of Eurocode EN 1998-3 on the secant stiffness at yield of structural r/c elements (EIsec), to properly simulate the extreme capable Near Collapse state of the building. Full details of the proposed methodology can be found in References[7,9,37].
2.1 End-section analysis of r/c elements
Given the geometry and reinforcement details of the end-sections of all structural elements, section analysis provides the 
2.2 Secant stiffness at yield of r/c elements
The secant stiffness at yield of the end-sections of each structural element is calculated according to EN 1998-3 (Informational 
Where My and θy are respectively the yield moment and the chord rotation at yield calculated in the previous step and Lv is the shear span, usually taken equal to half the clear length of the structural elements. The secant stiffness at yield to be assigned to each structural member of the non-linear model of the building is the average of the corresponding stiffness of their two end-sections for negative and positive bending.
2.3 Non-linear model. Definition of an ideal inelastic principal reference system of the multi-storey r/c building
The secant stiffness at yield must be assigned to each structural member in the nonlinear model of the r/c building. This is mandatory in EN 1998-3[38] for the verification in terms of deformations. The same rationale is adopted by the proposed procedure. This implies the formation of plastic hinges at both end-sections of all the structural members of the building model. But this is an ideal state, characterized by the authors as the extreme Capable Near Collapse state. By considering this state of full plastic mechanism at NC, the verification of the building is always on the safe side, because the building is more flexible, and the displacements and deformations are slightly enlarged at the NC state. To simulate the locations of all possible plastic deformations in the nonlinear model, concentrated plastic hinges should be inserted at the critical end-sections of each structural member.
In the previously formed non-linear model, the following must be determined: (a) the inelastic Centre of Stiffness (CRsec) of the multistorey r/c building and, hence, the in-plan location of the inelastic vertical Principal Axis (IIIsec) passing through it, (b) the inelastic horizontal Principal Axes (Isec, IIsec) of the multistorey r/c building, (c) the inelastic Torsional radii (γI,sec, γII,sec) of the multistorey r/c building. All the previously mentioned can be determined by performing a set of linear analyses, using the 
The (mean) torsional sensitivity of the multi-storey r/c building is verified by the following equation:
where 
2.4 Proposed vectors of floor enforced-displacements
Figure 1 and Figure 2 illustrate the proposed patterns in elevation of the seismic enforced interstorey drift ratios γI;II and of the seismic floor enforced-rotations ψR,III used in the framework of the proposed procedure for the verification of the building at the performance level of NC. These enforced displacements are the outcome of a large parametric analysis in various regular in elevation, ductile, multi-storey r/c buildings designed according to EN 1998-1 for Ductility Class High, by performing nonlinear response history analysis (N-LRHA) and always considering the influence of P-Delta effects. The parameters examined were the structure type (as defined in EN 1998-1[3]), the number of floors, the inelastic statistic eccentricity and the torsional sensitivity. The proposed values of Figure 1 and Figure 2 are mean values determined through a statistical processing.

Figure 1. Proposed seismic enforced interstorey drift ratios γI,i, or γII,i, (rad) in elevation for the NC performance level, at the location of the vertical axis IIIsec and along the horizontal directions Isec and IIsec (all cases of inelastic static eccentricity and torsional sensitivity). NC: near collapse.

Figure 2. Proposed seismic floor enforced-rotations ψR,III,i (rad) about vertical axis in elevation for the NC performance level (all cases of inelastic static eccentricity). NC: near collapse.
In Figure 1 and Figure 2, Hi/Hn is the relative height of the examined level (Hi, measured from the ground level) to the total building height Hn. Linear interpolation can be performed for intermediate number of stories. The parameters used in Figure 1 are the structural type and the number of stories. In Figure 2, the torsional sensitivity is an additional parameter (TF for torsionally flexible buildings and TS for torsionally stiff buildings). Figure 1 and Figure 2 provide proposed patterns of γI;II and ψR,III along each horizontal direction Isec and IIsec, separately. Then, the unique values of the i-floor enforced-rotations ψR,III,i are obtained as the average of the corresponding values along each horizontal direction. The proposed values of seismic enforced interstorey drift ratios γI;II (rad) in elevation are converted to floor enforced translational displacements ψI;II using the following equations:
Where H is the floor height. It is noted that the value of γI,II,i·Hi gives directly the i-floor seismic drift along the horizontal direction Isec or IIsec. The proposed values of floor enforced-displacements given by Eq. 3 are further adapted to the building under seismic evaluation following the procedure of the next step.
2.5 Temporary nonlinear static analyses along the ideal principal axes Isec and IIsec of the multi-storey building
The proposed patterns of floor enforced interstorey drift ratios γI;II can be adapted more specifically to the examined r/c multi-storey building by the envelope of two temporary sets of pushover analyses (with lateral floor forces and considering the P-Delta effects) along the horizontal directions Isec and IIsec. In the first set of pushover analyses (2 analyses along the Isec axis and more 2 analyses along the IIsec axis, considering the two signs (±) of application of the floor lateral forces), the floor lateral forces are applied at the location of the vertical IIIsec axis having a pattern according to the first uncoupled fundamental translational mode along each horizontal ideal direction, Isec or IIsec.
The second set of pushover analyses is similar to the first (2 analyses along the Isec axis and 2 analyses along the IIsec axis, considering the two signs (±) of application of the floor lateral forces) with the difference that only the 80% of the base shear is used, while the remainder 20% of the base shear is applied as a concentrated lateral load at the top of the vertical IIIsec axis. In both sets, the value of the base shear that is distributed in elevation can be considered equal to one (unit base shear). The target displacement of the two temporary sets of pushovers can be obtained from Table 1. This table contains the results of a large parametric analysis on 
| Number of Storeys | 1 | 2 | 5 | 10 | 15 | 
| Pure frame buildings without walls | 0.0300 | 0.0295 | 0.0235 | 0.0205 | 0.0195 | 
| Pure wall buildings without frames | 0.0280 | 0.0290 | 0.0260 | 0.0240 | 0.0230 | 
2.6 Enforced-displacement combinations to consider the spatial action of the earthquake
To consider the spatial character of the seismic action, the three enforced-displacements ψI,i, ψII,i and ψR,III,i should act simultaneously on the location of the vertical IIIsec axis inside each i-floor but with an appropriate way along each main loading direction 
| Eight (8) enforced-displacement combinations of nonlinear static analysis | |
| “+”ψI,i “+”0.3·ψII,i “+”ΨR,III,i | “+”ψI,i “+”0.3·ψII,i “-”ΨR,III,i | 
| “+”ψI,i “-”0.3·ψII,i “+”ΨR,III,i | “+”ψI,i “-”0.3·ψII,i “-”ΨR,III,i | 
| “-”ψI,i “+”0.3·ψII,i “+”ΨR,III,i | “-”ψI,i “+”0.3·ψII,i “-”ΨR,III,i | 
| “-”ψI,i “-”0.3·ψII,i “+”ΨR,III,i | “-”ψI,i “-”0.3·ψII,i “-”ΨR,III,i | 
| Eight (8) enforced-displacement combinations of nonlinear static analysis | |
| “+”0.3·ψI,i “+”ΨII,i “+”ΨR,III,i | “+”0.3·ψI,i “+”ΨII,i “-”ΨR,III,i | 
| “+”0.3·ψI,i “-”ΨII,i “+”ΨR,III,i | “+”0.3·ψI,i “-”ΨII,i “-”ΨR,III,i | 
| “-”0.3·ψI,i “+”ΨII,i “+”ΨR,III,i | “-”0.3·ψI,i “+”ΨII,i “-”ΨR,III,i | 
| “-”0.3·ψI,i “-”ΨII,i “+”ΨR,III,i | “-”0.3·ψI,i “-”ΨII,i “-”ΨR,III,i | 
2.7 Estimation of the seismic demand
The sixteen final pushover analyses of Table 2 and Table 3 are performed using as target displacement the value of the enforced translational displacement at the top of the vertical axis IIIsec, along each main loading direction Isec and IIsec. Therefore, the target displacement is equal to the value ψI;II,n calculated by Eq. 3b, where n is the top floor. The envelope of the response of the sixteen pushover analyses of the proposed procedure provides a safe prediction of the seismic demand at the NC state, especially as regards the interstorey drift ratios. The floor displacements are computed slightly conservatively in multi-storey buildings with more than three floors and are corrected according to the next step.
2.8 Correction of the floor displacement profiles
Since the goal of the proposed pushover procedure with floor enforced-displacements is to capture the maximum interstorey drift ratios of each floor-diaphragm, the estimates for the floor seismic displacement profiles will be slightly conservative, especially from the middle height of a multi-storey building to its top[1]. The abovementioned issue can be observed in multi-storey buildings with more than three floors. This is inevitable, since the floor enforced-displacements ψI;II are calculated sequentially with Eq. 3, from the base of the building to its top, through the proposed interstorey drift ratios γI,II which estimated conservatively in the parametric analysis with N-LRHA and express the maximum seismic interstorey drift ratios observed in the different floors of the building. However, these maximum values of interstorey drift ratios do not occur simultaneously.
To correct this conservatism, the values of γt,top in Table 1 can be used as a weighting factor on the value of the enforced translational displacement ψI;II,n at the top of the building calculated by Eq. 3. Therefore, the following reduction factor Su is proposed to apply totally on the floor displacement profiles along the Isec and IIsec axes[37]:
Where Hn is the total height of the building, γt,top is taken from Table 1 and ψn is calculated by Eq. 3. The use of the reduction factor Su is proposed for multi-storey buildings with four or more floors. The decrease shown on the floor displacement profiles by this factor is about 7-15%, where the largest values apply to high-rise buildings.
3. Numerical Example of a 6-storey Dual Building
3.1 Building characteristics
The six-storey r/c building shown in Figure 3 is examined to verify the proposed pushover procedure on torsionally flexible 
3.2 Building design
The building is designed according to the provisions of EN 1992-1 and EN 1998-1 for Ductility Class High. Modal response spectrum analysis was performed in the linear building model with PGA = 0.24 g (where g is the gravity acceleration), soil category D and total behavior factor q = 4.
All the structural members of the linear model have been provided with their effective flexural and shear stiffness, equal to one-half of their respective geometric stiffness. The building is classified into the structural type of dual buildings, equivalent to frame buildings according to EN1998-1, along both the horizontal ideal principal axes Ides and IIdes. The translational uncoupled periods of the linear model are 1.15 sec along the IIdes axis and 1.05 sec along the Ides axis. The horizontal ideal principal axes Ides and IIdes of the linear model are rotated relative to the x,y-axes by 14.06o counterclockwise. The two static eccentricities eI,des and eII,des along the Ides and 
3.3 Non-linear model of the building
Section analysis is performed by the module Section Designer of the FEM program SAP2000[52] which is used as the analysis tool. Having the Μ-φ curves along the local axes of the end-sections of all the structural members, as well as their shear span Lv and the plastic hinge length Lpl by the Eq. A9 of EN 1998-3 (with γel coefficient equal to 1.7), we can obtain the respective Μ-θ curves and subsequently calculate the secant stiffness at yield EIsec of all the structural members of the nonlinear building model (Eq. 1). The mean values in elevation of the ratio EIsec/EIg for each type of structural member of the nonlinear model are shown in Table 4, where EIg is the geometric stiffness. These values vary along the two local axes of columns and walls (2 and 3 axes) due to the different shear span Lv in four columns with cantilever bending mode and due to the different strength My and shear span Lv along the strong (axis 3) and weak (axis 2) directions of walls. We can observe the low values of the members’ bending stiffness, especially those of beams. These EIsec values are assigned to all the structural members of the nonlinear building model.
| Columns | Walls | Beams | |||
| storey | Local 3 | Local 2 | Local 3 | Local 2 | Local 3 | 
| 1 | 0.16 | 0.19 | 0.30 | 0.21 | 0.105 | 
| 2 | 0.15 | 0.19 | 0.27 | 0.20 | 0.110 | 
| 3 | 0.15 | 0.18 | 0.20 | 0.15 | 0.110 | 
| 4 | 0.12 | 0.13 | 0.16 | 0.13 | 0.095 | 
| 5 | 0.11 | 0.12 | 0.11 | 0.10 | 0.085 | 
| 6 | 0.10 | 0.10 | 0.07 | 0.08 | 0.075 | 
The “Capable Near Collapse Principal System, IIIsec(CRsec), Isec, IIsec” of the six-story r/c building is next determined according to Section 2, at the floor-diaphragm closest to the level 0.8 Htot = 16.8 m from the building base, i.e., at the fifth floor with height equal to 17.5 m from the ground. Figure 3 shows the in-plan location of the inelastic center of stiffness CRsec and the orientation of the horizontal ideal inelastic principal axes C, IIsec in the nonlinear building model.
The latter are turned relative to the x, y-axes by 11.5o counterclockwise. The inelastic static eccentricities are equal to eR,Isec = 2.3 m and eR,Isec = 2.63 m and their normalized values are equal to eR,Isec/ LIsec = 0.09 and eR,IIsec/ LIsec = -0.013, where LIsec and LIIsec are the maximum plan dimensions along the axes Isec and IIsec, respectively. The (mean) normalized inelastic torsional radii are equal to 
| UncoupledMode | Period (sec) | UX | UY | RZ | CoupledMode | Period (sec) | UX | UY | RZ | 
| 1 | 2.233 | 0.030 | 0.753 | 0.002 | 1 | 2.478 | 0.062 | 0.441 | 0.309 | 
| 2 | 2.109 | 0.006 | 0.000 | 0.786 | 2 | 2.132 | 0.461 | 0.238 | 0.086 | 
| 3 | 1.998 | 0.745 | 0.030 | 0.002 | 3 | 1.782 | 0.261 | 0.108 | 0.385 | 
| 4 | 0.726 | 0.002 | 0.082 | 0.024 | 4 | 0.832 | 0.011 | 0.050 | 0.045 | 
| 5 | 0.697 | 0.031 | 0.016 | 0.065 | 5 | 0.699 | 0.069 | 0.039 | 0.006 | 
| 6 | 0.645 | 0.083 | 0.017 | 0.024 | 6 | 0.562 | 0.035 | 0.025 | 0.065 | 
| 7 | 0.404 | 0.001 | 0.017 | 0.023 | 7 | 0.469 | 0.005 | 0.017 | 0.019 | 
| 8 | 0.376 | 0.023 | 0.020 | 0.006 | 8 | 0.375 | 0.029 | 0.018 | 0.001 | 
| 9 | 0.324 | 0.025 | 0.013 | 0.018 | 9 | 0.312 | 0.004 | 0.010 | 0.008 | 
Finally, point hinges of type M3 (pure bending) and P-M2-M3 (biaxial bending with axial force) are inserted at the end-sections of each beam and column/wall of the nonlinear model, respectively, with constitutive laws according to Mander et al.[53] for the unconfined/confined concrete and according to Park and Paulay[54] for the steel reinforcement. The backbone curves of the response of the fiber hinges at the end-sections of the structural elements (determined from the abovementioned constitutive laws) and the Takeda and the Kinematic hysteresis model for the concrete and the steel rebars respectively are embedded in the SAP2000 FEM program used for the nonlinear analysis. Additional information can be found in SAP2000 analysis manual.
It is noted that accidental eccentricity was not considered in nonlinear analysis. As was observed in the extended parametric analysis of regular in elevation, ductile, asymmetric, r/c multi-storey buildings implemented in the doctoral dissertation of the first author[37], the value of the accidental eccentricity proposed by the seismic codes has only a very minor impact on the nonlinear response in the deep nonlinear area (Near Collapse).
3.4 Seismic demand
The inertial characteristics of the nonlinear model of the six-storey building are concentrated at the geometric centre of each i-floor 

Figure 5. Mean spectrum of artificial accelerograms vs EN 1998-1 design elastic spectrum (ξ = 0.05, PGA = 0.4 g, soil D).
| Accelerogram | A1 | A2 | A3 | A4 | A5 | A6 | A7 | A8 | A9 | A10 | A11 | 
| Max Acceleration (g) | 0.99 | 1.00 | 1.00 | 1.00 | 1.00 | 0.99 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 
| Max Velocity (cm/sec) | 241.85 | 151.42 | 179.28 | 149.63 | 162.71 | 156.34 | 191.53 | 221.30 | 184.26 | 178.82 | 188.13 | 
| Max Displacement (cm) | 384.42 | 54.71 | 75.47 | 140.46 | 65.88 | 75.65 | 126.50 | 480.58 | 187.09 | 166.50 | 192.27 | 
| Vmax/Amax (sec) | 0.25 | 0.15 | 0.18 | 0.15 | 0.17 | 0.16 | 0.19 | 0.23 | 0.19 | 0.18 | 0.19 | 
| Acceleration RMS (g) | 0.27 | 0.26 | 0.27 | 0.26 | 0.28 | 0.27 | 0.28 | 0.27 | 0.25 | 0.27 | 0.25 | 
| Velocity RMS (cm/sec) | 77.00 | 40.54 | 40.63 | 48.44 | 38.11 | 42.28 | 47.47 | 87.01 | 58.57 | 54.89 | 50.95 | 
| Displacement RMS (cm) | 166.57 | 17.61 | 23.55 | 63.49 | 23.07 | 29.74 | 61.28 | 239.80 | 113.63 | 77.57 | 92.26 | 
| Arias Intensity (m/sec) | 29.03 | 26.03 | 28.74 | 26.66 | 29.23 | 28.31 | 29.19 | 27.39 | 24.46 | 28.38 | 24.42 | 
| Characteristic Intensity | 0.72 | 0.66 | 0.71 | 0.67 | 0.72 | 0.71 | 0.72 | 0.69 | 0.63 | 0.71 | 0.63 | 
| Specific Energy Density (cm2/sec) | 148,285 | 41,107 | 41,277 | 58,686 | 36,315 | 44,707 | 56,346 | 189,336 | 85,781 | 75,357 | 64,929 | 
| Cum. Abs. Velocity (cm/sec) | 4,743.6 | 4,405.2 | 4,666.4 | 4,348.7 | 4,642.8 | 4,951. | 4,915.3 | 4,718.9 | 4,501.6 | 4,716.0 | 4,389.4 | 
| Acc Spectrum Intensity (g*sec) | 0.96 | 0.95 | 0.95 | 0.94 | 0.95 | 0.96 | 0.95 | 0.96 | 0.96 | 0.96 | 0.95 | 
| Vel Spectrum Intensity (cm) | 654.10 | 659.10 | 646.44 | 653.68 | 644.19 | 636.91 | 662.37 | 628.21 | 648.40 | 643.51 | 661.66 | 
| Housner Intensity (cm) | 629.25 | 634.98 | 611.72 | 637.95 | 614.88 | 623.84 | 641.22 | 616.83 | 639.60 | 643.14 | 636.73 | 
| Sustained Max.Acceleration (g) | 0.93 | 0.95 | 0.99 | 0.98 | 0.97 | 0.92 | 0.98 | 0.92 | 0.99 | 0.93 | 0.96 | 
| Sustained Max.Velocity (cm/sec) | 178.42 | 121.72 | 110.04 | 139.51 | 114.05 | 132.98 | 124.22 | 170.09 | 162.42 | 144.99 | 115.79 | 
| Effective Design Acceleration (g) | 0.93 | 0.95 | 1.02 | 0.99 | 1.03 | 0.99 | 1.01 | 0.94 | 1.02 | 0.97 | 1.00 | 
| A95 parameter (g) | 0.95 | 0.99 | 0.98 | 0.98 | 0.98 | 0.98 | 0.98 | 0.98 | 0.99 | 0.99 | 0.99 | 
| Predominant Period (sec) | 0.56 | 0.30 | 0.24 | 0.30 | 0.58 | 0.74 | 0.72 | 0.24 | 0.72 | 0.72 | 0.26 | 
| Significant Duration (sec) | 14.93 | 14.14 | 14.93 | 14.17 | 14.11 | 18.05 | 17.30 | 17.28 | 17.24 | 16.15 | 14.64 | 
3.5 Proposed interstorey drift ratios and floor enforced-rotations
For the implementation of the proposed procedure of pushover analysis, the initially proposed interstorey drift ratios γI,i,II at the 

Figure 6. Proposed values of (a) Interstorey drift ratios γI;II (rad); (b) Floor enforced-rotationsψR,III (rad).
3.6 Two temporary sets of pushover analysis to calculate the final proposed floor enforced translations
Two temporary sets of pushover analysis (with forces) are performed to find revised values of interstorey drift ratios rI,i, rII,i. The pattern of floor lateral forces in the two sets, which are applied at the in-plan location of the vertical axis IIIsec along the (±) directions of the horizontal Isec and IIsec axes, is depicted in Figure 7.

Figure 7. Pattern of floor lateral static loads on the in-plan location of the vertical IIIsec axis and along the horizontal Isec and IIsec axes. (a) First temporary set of (4) pushover analyses; (b) Second temporary set of (4) pushover analyses.
These floor forces correspond to a unit base shear that is distributed in elevation according to the translational building modes along the Isec and IIsec axes in both sets but with an additional top force in the second set equal to 20% of the base shear. The target displacement at the top of the vertical axis IIIsec, along both the Isec and IIsec axes, is calculated directly from Table 1 by double linear interpolation for multi-storey buildings with six floors and with a dual structural system: 
It is noted that the envelope of the displacement results from N-LRHA provides a displacement at the top of the vertical axis IIIsec equal to 0.574 m along both the Isec and IIsec axes, which is greater from the previous one (the mean displacements from N-LRHA at the same point are about 0.40 m along both the horizontal principal directions). Additionally, by performing the methodology of 
The envelope of the interstorey drift ratios rI,i, rII,i resulted from the eight total pushovers of the two temporary sets is shown in 
| Interstorey drift ratiosγI,i and γII,i (rad) | ||||||||
| Temp. Pushovers ENV | Prop. Values, Figure 6 | Final proposed values | Floor enforced displacements | |||||
| Dir Isec | Dir IIsec | Dir Isec, IIsec | Dir Isec | Dir IIsec | ψI,i (m) | ψII,i (m) | ψR,III,i (rad) | |
| 1st | 0.0240 | 0.0209 | 0.0234 | 0.0237 | 0.0222 | 0.083 | 0.078 | 0.0033 | 
| 2nd | 0.0328 | 0.0327 | 0.0292 | 0.0310 | 0.0309 | 0.191 | 0.186 | 0.0064 | 
| 3rd | 0.0322 | 0.0339 | 0.0292 | 0.0307 | 0.0315 | 0.299 | 0.296 | 0.0096 | 
| 4th | 0.0283 | 0.0293 | 0.0292 | 0.0287 | 0.0292 | 0.399 | 0.398 | 0.0128 | 
| 5th | 0.0233 | 0.0229 | 0.0275 | 0.0254 | 0.0252 | 0.488 | 0.487 | 0.0159 | 
| 6th | 0.0169 | 0.0162 | 0.0220 | 0.0194 | 0.0191 | 0.556 | 0.553 | 0.0182 | 
3.7 Proposed pushover procedure for the estimation of the seismic demand. Verification
The sixteen pushovers of Table 2 and Table 3 are performed with target displacement along the main loading directions Isec and IIsec equal to ψI,6 = 0.556 m and ψII,6 = 0.556 m (Table 7). The envelope of the response from the 16 pushover analyses of the proposed pushover procedure can be considered as an estimation of the seismic demand.
The effectiveness of the proposed pushover procedure on the prediction of seismic demand will be verified against the results of 
The patterns of interstorey drift ratios in elevation, at the flexible and stiff sides of the building as well as at the location of CM and that of the vertical IIIsec axis (CRsec) inside each floor, are presented in Figure 8. The (%) errors committed on the estimation of the seismic demand (N-LRHA) by the proposed and the Extended N2 pushovers are recorded in Table 8, where the (–) sign indicates unconservative estimates. It is obvious from Figure 8 that the N2 pushover procedure seriously underestimates the interstorey drift ratios at the stiff sides of the building, all over its height. It also underestimates the interstorey drift ratios at any location in the upper half of the building.

Figure 8. Interstorey drift ratios. Proposed pushover procedure vs. Ν-LRHA and Extended N2 pushover.
| Pushover with Enforced Displacements | Pushover Extended N2 | |||||||||
| Direction IIsec | Floor | CM | CR | Stiff Side | Flex Side | CM | CR | Stiff Side | Flex Side | |
| 1 | 2 | -10 | -3 | 3 | -7 | -11 | -20 | -12 | ||
| 2 | -6 | -8 | -1 | -6 | 4 | 6 | -2 | 14 | ||
| 3 | -2 | -8 | 7 | 0 | 9 | 8 | 11 | 19 | ||
| 4 | -13 | -19 | 2 | -2 | -11 | -12 | 3 | 1 | ||
| 5 | -12 | -17 | -3 | -1 | -9 | -7 | 6 | -7 | ||
| 6 | -7 | -13 | -2 | 2 | -2 | 2 | 19 | -9 | ||
| Direction Isec | Floor | CM | CR | Stiff Side | Flex Side | CM | CR | Stiff Side | Flex Side | |
| 1 | 1 | -5 | 12 | 13 | 10 | 9 | 6 | 33 | ||
| 2 | 8 | 1 | 12 | 0 | 26 | 20 | 13 | 39 | ||
| 3 | -5 | -12 | 7 | -2 | 6 | 1 | 6 | 25 | ||
| 4 | -12 | -16 | 7 | 0 | -7 | -8 | 6 | 14 | ||
| 5 | 0 | -6 | 8 | 2 | 5 | 6 | 14 | 8 | ||
| 6 | 10 | 8 | 16 | 11 | 14 | 22 | 30 | 10 | ||
On the contrary, N2 pushover overestimates in general the interstorey drift ratios at any location (except the stiff sides) in the lower half of the building (2nd and 3rd floor). We can also see from Figure 8 and Table 8 that the seismic interstorey drift ratios at the flexible and stiff sides of the six-storey building are safely or marginally estimated by the proposed pushover procedure. These estimates are more balanced than those of the Extended N2 pushover, which provides in general more conservative estimates but also some unconservative ones along the IIsec axis at the first floor. At the in-plan location of CRsec, the seismic interstorey drift ratios are in general slightly underestimated by the proposed procedure due to the smaller value of the target (enforced) displacements used in pushover analysis compared to the corresponding N-LRHA displacements. But at the in-plan location of CM the interstorey drift ratios are in general marginally estimated.
According to Section 2, the floor displacements computed by the proposed pushover procedure must be totally reduced by the factor Su of Eq. 4: 
Where rt,top · Hn =0.515 m is the proposed top target displacement of the temporary pushovers from Table 1 previously calculated and ψI;II,6 = 0.556 or 0.553 m is the enforced translational displacement of the building top (Table 7). In Figure 9, the floor displacements profiles resulted by the proposed pushover procedure compare with the corresponding ones by N-LRHA and Extended N2 pushover.

Figure 9. Floor displacement profiles. Proposed pushover procedure vs. Ν-LRHA and extended N2 pushover.
The (%) errors committed on the estimation of the seismic demand are recorded in Table 9. We observe that, at the in-plan location of the vertical IIIsec axis (CRsec) the floor displacements are slightly underestimated by the proposed procedure. This is due to the smaller value of the target (enforced) displacements used in pushover analysis compared to the corresponding N-LRHA displacements and due to the above reduction by the factor Su. But at the in-plan location of CM, the floor displacements are in general marginally estimated. Slightly conservative or marginal estimates of the floor displacements from the proposed pushover procedure are observed on the stiff and flexible sides of the six-storey building. The Extended N2 pushover provides in general more conservative estimates of the floor displacements on the flexible sides of the building but also some unconservative ones on the stiff side of the first floor of the building along the IIsec axis.
| Pushover with Enforced Displacements | Pushover Extended N2 | |||||||||
| Direction IIsec | Floor | CM | CR | Stiff Side | Flex Side | CM | CR | Stiff Side | Flex Side | |
| 1 | -5 | -16 | -10 | -5 | -7 | -11 | -20 | -12 | ||
| 2 | -9 | -15 | -9 | -6 | 0 | -1 | -10 | 6 | ||
| 3 | -8 | -12 | -5 | -3 | 5 | 5 | -1 | 15 | ||
| 4 | -4 | -8 | 2 | 4 | 7 | 8 | 6 | 20 | ||
| 5 | -1 | -9 | 7 | 10 | 5 | 2 | 7 | 18 | ||
| 6 | 0 | -9 | 9 | 12 | 0 | -3 | 5 | 12 | ||
| Direction IIsec | Floor | CM | CR | Stiff Side | Flex Side | CM | CR | Stiff Side | Flex Side | |
| 1 | -6 | -12 | 4 | 5 | 10 | 9 | 6 | 33 | ||
| 2 | -2 | -7 | 4 | -1 | 19 | 17 | 11 | 37 | ||
| 3 | 3 | -7 | 7 | 5 | 25 | 16 | 14 | 45 | ||
| 4 | -3 | -11 | 6 | 9 | 12 | 6 | 9 | 43 | ||
| 5 | -4 | -11 | 8 | 16 | 4 | -1 | 6 | 40 | ||
| 6 | -2 | -9 | 12 | 18 | 0 | -4 | 5 | 33 | ||
The capacity curves of the sixteen pushovers with enforced-displacements are shown in Figure 10. The slope of the initial (elastic) branch and the ultimate and yield values of the base shear and top displacement of the building are different in each curve, depending mainly on the (±) action of the floor enforced-rotations. These curves are first bi-linearized and then can be used to connect the seismic capacity (pushover results) with the seismic demand (earthquake action) by using the informational Annex B of EN 1998-1 or any other acceptable method. By knowing the pattern of floor enforced translational displacements ψI;II in elevation and the corresponding target displacement on the building top, the backwards application of EN1998-1 Annex B gives the maximum (capable) earthquake in PGA terms that the building can attain (NC state). In our case, this PGA is equal to about 0.40 g, which is the same value used in N-LRHA.
Finally, the plastic mechanism of the six-storey building (which is of beam-type) is safely predicted by the envelope of the sixteen pushovers of the proposed procedure. As regards the plastic chord rotations developed at the end-sections of the structural elements, they are fully compatible with the computed interstorey drift ratios which have been in general safely estimated.
4. Conclusions
An asymmetric, torsional flexible, regular in elevation, ductile, six-storey r/c building was seismically accessed here by a recently proposed pushover procedure with floor enforced-displacements to verify its effectiveness.
According to the proposed pushover procedure, a pattern of seismic floor-enforced displacements (two translational displacements and a rotational one) properly combined with each other to consider the spatial seismic action is applied and a set of sixteen pushovers is performed. The envelope of the sixteen pushovers provides a safe estimate of the seismic demand at the NC state of the building. Appropriate seismic, drift-based, floor enforced-displacements are proposed that lead the building at the attainment of the NC state. The proposed values of the floor translational displacements are further revised through two temporary sets of pushovers. All analyses in the framework of the proposed pushover procedure are implemented with respect to an ideal, inelastic, 3D principal reference system CRsec (Isec, IIsec, IIIsec), which is called “Capable Near Collapse Principal System of the multi-storey r/c building”. This system is determined by applying the torsional optimum axis methodology to the nonlinear model of the building in which all structural members have been supplied with the secant stiffness at yield EIsec. Additionally, a new criterion is used for the verification of the torsional sensitivity of the building in the non-linear area.
To verify the effectiveness of the proposed procedure on the prediction of the seismic demand, nonlinear response history analysis (N-LRHA) with 14 pairs of artificial accelerograms has been performed to provide the seismic demand at the attainment of the NC state of the six-storey r/c building. From the comparison of the response computed by the proposed pushover procedure and by the (envelope of) N-LRHA, the main conclusions are:
The seismic interstorey drift-ratios on the stiff and flexible sides of the building are safely estimated by the proposed procedure. In other locations, such as those of CM and CRsec, the interstorey drift ratios are marginally estimated or slightly underestimated. Hence, the main objective of the proposed procedure, which is the complete control of the distribution -in plan and in elevation- of the seismic structural damage at the NC state, is fully achieved.
The seismic floor displacement profiles on the stiff and flexible sides of the building are safely estimated by the proposed procedure. In other locations, such as those of CM and CRsec, the floor displacements are marginally estimated or slightly underestimated.
The plastic chord rotations at the end-sections of the structural members are also safely estimated in general by the proposed procedure, following the safe estimation of the seismic interstorey drift ratios.
The plastic mechanism of the building at the NC state is fully captured by the envelope of the sixteen pushover analyses in the framework of the proposed procedure.
Therefore, the proposed enforced-displacement pushover procedure is a simple and effective tool for the seismic assessment of asymmetric, torsional flexible, regular in elevation, ductile multistorey r/c buildings. The effectiveness of the proposed pushover procedure with enforced displacements has been fully evaluated in the first author’s doctoral dissertation[37] by examining various regular in elevation, ductile, multistorey r/c buildings with varying number of floors, structural type, static eccentricity and torsional sensitivity. In other words, the proposed procedure can be successfully used to seismically assess any type of asymmetric 
Supplementary materials
The supplementary material for this article is available at: Supplementary materials.
Authors contribution
All authors contributed equally to this work.
Conflicts of Interest
Triantafyllos K. Makarios is an Editorial Board member of Journal of Building Design and Environment, and other authors declare no conflict of interest.
Ethical approval
Not applicable.
Consent to participate
Not applicable.
Consent for publication
Not applicable.
Availability of data and materials
Not applicable.
Funding
None.
Copyright
© The Author(s) 2023.
References
- 
										1. Gupta A, Krawinkler H. Seismic demands for performance evaluation of steel moment resisting frame structures. John A Blume Earthquake Engineering Center Technical Report 132; 199.
- 
										2. Goel RK. Evaluation of nonlinear static procedures using building strong motion records. In: Wallace JW, editor. Structural Engineering Research Frontiers. Reston: American Society of Civil Engineers; 2012. p. 1-12.[DOI]
- 
										3. Eurocode 8: Design of structures for earthquake resistance-Part 1: General rules, seismic actions and rules for buildings; 2004. Available from: https://www.confinedmasonry.org/wp-content/uploads/2009/09/Eurocode-8-1-Earthquakes-general.pdf
- 
										4. Bakalis A, Makarios T. Dynamic eccentricities in pushover analysis of asymmetric single-storey buildings. In: Köber D, De Stefano M, Zembaty Z, editors. Seismic Behaviour and Design of Irregular and Complex Civil Structures III. Cham: Springer; 2020. p. 307-320.[DOI]
- 
										5. Bakalis AP, Makarios ΤK. Dynamic eccentricities and the “capable near collapse centre of stiffness” of reinforced concrete single-storey buildings in pushover analysis. Eng Struct. 2018;166:62-78.[DOI]
- 
										6. Bakalis AP, Makarios ΤK. Seismic assessment of asymmetric single-story RC buildings by modified pushover analysis using the “Capable Near Collapse Centre of Stiffness”: Validation of the method. J Earthq Eng. 2022;26(2):980-1009.[DOI]
- 
										7. Bakalis AP, Makarios ΤK . Seismic enforced-displacement pushover procedure on multistorey R/C buildings. Eng Struct. 2021;229:111631[DOI]
- 
										8. Makarios T, Bakalis AP. Pushover analysis using suitable dynamic eccentricities on asymmetric single-storey buildings. Engineering. 2018. Available from: https://www.semanticscholar.org/paper/PUSHOVER-ANALYSIS-USING-SUITABLE-DYNAMIC-ON-Makarios-Bakalis/04f7eacadaeb8d8bd776f3366e3b807b267d5b63
- 
										9. Makarios T, Bakalis A. Seismic enforced displacement-based pushover analysis on irregular in-plan R/C multi-storey buildings. In: Bento R, De Stefano M, Köber D, Zembaty Z, editors. Seismic Behaviour and Design of Irregular and Complex Civil Structures IV. Cham: Springer; 2022. p. 37-47.[DOI]
- 
										10. Bakalis A, Makarios T, Athanatopoulou A. Inelastic dynamic eccentricities in pushover analysis procedure of multi-story RC buildings. Buildings. 2021;11(5):195.[DOI]
- 
										11. Chopra AK, Goel RK. A modal pushover analysis procedure to estimate seismic demands for unsymmetric-plan buildings. Earthq Eng Struct Dyn. 2004;33(8):903-927.[DOI]
- 
										12. Reyes JC, Chopra AK. Three-dimensional modal pushover analysis of buildings subjected to two components of ground motion, including its evaluation for tall buildings. Earthq Eng Struct Dyn. 2011;40:789-806.[DOI]
- 
										13. Hernandez-Montes E, Kwon OS, Aschheim MA. An energy-based formulation for first and multiple-mode nonlinear static (pushover) analyses. J Earthq Eng. 2004;8(1):69-88.[DOI]
- 
										14. Lin JL, Tsai KC. Seismic analysis of two-way asymmetric building systems under bi-directional seismic ground motions. Earthq Eng Struct Dyn. 2008;37(2):305-328.[DOI]
- 
										15. Manoukas G, Athanatopoulou A, Avramidis I. Multimode pushover analysis for asymmetric buildings under biaxial seismic excitation based on a new concept of the equivalent single degree of freedom system. Soil Dyn Earthq Eng. 2012;38:88-96.[DOI]
- 
										16. Fujii K. Prediction of the largest peak nonlinear seismic response of asymmetric buildings under bi-directional excitation using pushover analyses. Bull Earthq Eng. 2014;12:909-938.[DOI]
- 
										17. Soleimani S, Aziminejad A, Moghadam AS. Extending the concept of energy-based pushover analysis to assess seismic demands of asymmetric-plan buildings. Soil Dyn Earthq Eng. 2017;93:29-41.[DOI]
- 
										18. Fajfar P, Marusic D, Perus I. Torsional effects in the pushover-based seismic analysis of buildings. J Earthq Eng. 2005;9(6):831-854.[DOI]
- 
										19. Kreslin M, Fajfar P. The extended N2 method considering higher mode effects in both plan and elevation. Bull Earthq Eng. 2012;10:695-715.[DOI]
- 
										20. Bhatt C, Bento R. Extension of the CSM-FEMA440 to plan-asymmetric real building structures. Earthq Eng Struct Dyn. 2011;40(11):1263-1282.[DOI]
- 
										21. Rofooei FR, Mirjalili MR. Dynamic-based pushover analysis for one-way plan-asymmetric buildings. Eng Struct. 2018;163:332-346.[DOI]
- 
										22. Bosco M, Ghersi A, Marino EM. Corrective eccentricities for assessment by the nonlinear static method of 3D structures subjected to bidirectional ground motions. Earthq Eng Struct Dyn. 2012;41(13):1751-1773.[DOI]
- 
										23. Bosco M, Ghersi A, Marino EM, Rossi PP. Generalized corrective eccentricities for nonlinear static analysis of buildings with framed or braced structure. Bull Earthq Eng. 2017;15:4887-4913.[DOI]
- 
										24. Antoniou S, Pinho R. Advantages and limitations of adaptive and non-adaptive force-based pushover procedures. J Earthq Eng. 2004;8(4):497-522.[DOI]
- 
										25. Antoniou S, Pinho R. Development and verification of a displacement-based adaptive pushover procedure. J Earthq Eng. 2004;8(5):643-661.[DOI]
- 
										26. Kalkan E, Kunnath SK. Adaptive modal combination procedure for nonlinear static analysis of building structures. J Struct Eng. 2006;132(11):1721-1731.[DOI]
- 
										27. Bhatt C, Bento R. The extended adaptive capacity spectrum method for the seismic assessment of plan-asymmetric buildings. Earthq Spectra. 2014;30(2):683-703.[DOI]
- 
										28. Amini MA, Poursha M. Adaptive force-based multimode pushover analysis for seismic evaluation of midrise buildings. J Struct Eng. 2018;144(8):04018093.[DOI]
- 
										29. Poursha M, Khoshnoudian F, Moghadam AS. The extended consecutive modal pushover procedure for estimating the seismic demands of two-way unsymmetric-plan tall buildings under influence of two horizontal components of ground motions. Soil Dyn Earthq Eng. 2014;63:162-173.[DOI]
- 
										30. Goel RK, Chopra AK. Evaluation of modal and FEMA pushover analyses: SAC buildings. Earthq Spectra. 2004;20(1):225-254.[DOI]
- 
										31. Erduran E. Assessment of current nonlinear static procedures on the estimation of torsional effects in low-rise frame buildings. Eng Struct. 2008;30(9):2548-2558.[DOI]
- 
										32. Baros DK, Anagnostopoulos SA. An overview of pushover procedures for the analysis of buildings susceptible to torsional behavior. In: The 14th World Conference on Earthquake Engineering; 2008 Oct 12-17; Beijing, China. Available from: http://www.iitk.ac.in/nicee/wcee/article/14_05-01-0195.PDF
- 
										33. Bento R, Bhatt C, Pinho R. Using nonlinear static procedures for seismic assessment of the 3D irregular SPEAR building. Earthq Struct. 2010;1(2):177-195.[DOI]
- 
										34. Bhatt C, Bento R. Comparison of nonlinear static methods for the seismic assessment of plan irregular frame buildings with non seismic details. J Earthq Eng. 2012;16(1):15-39.[DOI]
- 
										35. De Stefano M, Mariani V. Pushover analysis for plan irregular building structures. In: Ansal A, editor. Perspectives on European Earthquake Engineering and Seismology. Cham: Springer; 2014. p. 429-448.[DOI]
- 
										36. Anagnostopoulos SA, Kyrkos MT, Stathopoulos KG. Earthquake induced torsion in buildings: Critical review and state of the art. Earthq Struct. 2015;8(2):305-377.[DOI]
- 
										37. Bakalis A. Seismic non-linear static analysis of asymmetric reinforced concrete buildings at capable near collapse state using imposed floor displacements or inelastic dynamic eccentricities [dissertation]. Greece: University of Thessaloniki; 2021.
- 
										38. Eurocode 8: Design of structures for earthquake resistance-part 3: Assessment and retrofitting of buildings. European Committee for Standardization; 2005.
- 
										39. Makarios T, Anastassiadis K. Real and fictitious elastic axis of multi-storey buildings: Theory. Struct Des Tall Build. 1998;7(1):33-55.[DOI]
- 
										40. Makarios T, Anastassiadis K. Real and fictitious elastic axis of multi-storey buildings: Applications. Struct Des Tall Build. 1998;7(1):57-71.[DOI]
- 
										41. Makarios TK. Optimum torsion axis to multistory buildings by using the continuous model of the structure. J Struct Des Tall Spec Build. 2005;14(1):69-90.[DOI]
- 
										42. Makarios T. Practical calculation of the torsional stiffness radius of multistorey tall buildings. J Struct Des Tall Spec Build. 2008;17(1):39-65.[DOI]
- 
										43. Makarios T, Athanatopoulou AM, Xenidis H. Numerical verification of properties of the fictitious elastic axis in asymmetric multistorey buildings. J Struc Des Tall Spec Build. 2006;15(3):249-276,[DOI]
- 
										44. Athanatopoulou A, Doudoumis I. Principal directions under lateral loading in multistory asymmetric buildings. Struct Des Tall Spec Build. 2008;17(4):773-794.[DOI]
- 
										45. Marino EM, Rossi PP. Exact evaluation of the location of the optimum torsion axis. Struct Des Tall Spec Build. 2004;13(4):277-290.[DOI]
- 
										46. Georgoussis G. Modal eccentricities of asymmetric structures. Struct Des Tall Spec Build. 2006;15(3):339-361.[DOI]
- 
										47. Georgoussis G. An alternative approach for assessing eccentricities in asymmetric multistory buildings.1. Elastic systems. Struct Des Tall Spec Build. 2009;18(2):181-202.[DOI]
- 
										48. Georgoussis GK. Modal rigidity center: It’s use for assessing elastic torsion in asymmetric buildings. Earthq Struct J. 2010;1(2):163-175.[DOI]
- 
										49. Bosco M, Marino EM, Rossi PP. An analytical method for the evaluation of the in plan irregularity of non-regularity asymmetric buildings. Bull Earthq Eng. 2013;11(5):1423-1445.[DOI]
- 
										50. Hejal R, Chopra, AK. Earthquake response of torsionally-coupled buildings. Earthquake Eng Res Cent. 1989;18(3):305-323.[DOI]
- 
										51. Wilson EL. Eurocode 2. Design of concrete structures-Part 1-1: General rules and rules for buildings (2008).
- 
										52. Three dimensional static and dynamic finite element analysis and design of structures. Computers and Structures Inc; 2022. Available from: http://civilwares.free.fr/ForLinh/3D%20Static%20And%20Dynamic%20Analysis%20Of%20Structures%20-%20E%20Wilson.pdf
- 
										53. Mander JB, Priestley MJN, Park R. Theoretical stress-strain model for confined concrete. J Struct Eng. 1988;114(8):1827-1849.[DOI]
- 
										54. Park R, Paulay T. Reinforced concrete structures. New York: John Wiley & Sons, Inc; 1975.
- 
										55. Seismosoft-SeismoArtif. A Computer program for generating artificial earthquake accelerograms matched to a specific target response spectrum; 2016.
- 
										56. Makarios T. Design characteristic value of the Arias intensity magnitude for artificial accelerograms compatible with Hellenic seismic hazard zones. Int J Innov Res Adv Eng. 2015;2:87-98. Available from: https://www.semanticscholar.org/paper/Design-Characteristic-value-of-the-Arias-intensity-Makarios/a42903a9e76fe4708b3a3768dd04ece16410366a
- 
										57. Fajfar P. A nonlinear analysis method for performance-based seismic design. Earthq Spectra. 2000;16(3):573-592.[DOI]
Copyright
© The Author(s) 2023. This is an Open Access article licensed under a Creative Commons Attribution 4.0 International License (https://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, sharing, adaptation, distribution and reproduction in any medium or format, for any purpose, even commercially, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made.
Publisher’s Note
Share And Cite
Science Exploration Style
 Get citation
				Get citation
			Science Exploration Style
 
				 
				





